QUBe SQU-HT
QUBe SQU-HT
SQU-HT
- 4 physical sizes with 5 models from 315mm to 710mm.
- Air volume flow rates of up to 3.9 m3/s.
- Static pressures of up to 964 Pa.
- Interchangeable double skinned panels.Suitable for operating temperatures up to +120°C.
- Interchangeable double skinned.
Learn more about DCV
Compare
The QUBe SQU-HT is a multi-discharge, double skinned fan unit incorporating the high performance backward curved Ziehl-Abegg RH-C impeller designed specifically for operation without a scroll. With motor out of the airstream it is suitable for more arduous and elevated temperature applications. The unit is supplied as either an end inlet vertical discharge unit (QUBe-HT) or as a side inlet vertical discharge unit (QUBe-HTs)*.
*Please specify at the time of ordering.
Features & Benefits
Full accessory range
Flexible connectors, attenuators, Eltadrive VSD frequency inverter controls, Eltadrive VSD frequency inverters (1Ph and 3Ph supply).
Material strength
Self supporting corrosion-resistant extruded Aluminium section, assembled with aluminium corners ideally suited for elevated temperature applications.
Motor performance
Three phase multi-voltage IP55 TEFC motor, wound for either (Delta) 230V/3Ph/50Hz or (Star) 400V/3Ph/50Hz connection, which is mounted out of the airstream, suitable for speed control with the Eltadrive VSD range of frequency inverter controls. Customer connection direct to the IP55 motor terminal box.
Quality Impeller Design
High efficiency backward curved welded steel impeller with a non-overloading power characteristic, suitable for continuous S1 operation up to 120°C, finished with a powder coating to RAL 5002 for greater surface protection.
Choice
Straight through airflow as supplied. Discharge position can be altered on site.
Quality assurance
End inlet or side inlet with vertical discharge as supplied.
Ease of installation
An easily removable motor/impeller assembly arrangement, ideal for frequent cleaning or maintenance.

Specification
The Qube HT range of centrifugal box fans as manufactured by Elta Fans Ltd. 46 Third Avenue, Pensnett Trading Estate, Kingswinford, West Midlands, DY6 7US, UK. Tel: +44 (0) 1384 275800 - If you need more information - Visit demandcontrolventilation.com. Or contact us.
Casing
Constructed from self supporting corrosion-resistant extruded Aluminium section, assembled with shock resistant fibreglass reinforced Polyamide PA6 corners, and 25mm thick Double skinned fully inter-changeable removable panels, manufactured from pre-galvanised steel, in-filled with a non flammable mineral wool, 60kg/m3, thereby minimising breakout noise.
Motors
Three phase multi-voltage IP55 TEFC Foot / Flange mounted IEC frame motors, wound for either (Delta) 230V/3Ph/50Hz or (Star) at 400V/3Ph/50Hz connection, suitable for speed control when used with the Eltadrive VSD range of frequency inverter controls.
Motors are pre-wired to an IP55 terminal box mounted on the side, for easy customer connection.
Impellers
A high efficiency backward curved welded steel impeller with a non-overloading power characteristic, finished with a powder coating to RAL 5002 for greater surface protection, and dynamically balanced to G2.5 / G6.3 according to ISO1940 part 1.
Quality Management
Units are to be designed and manufactured with procedures as defined in BS EN ISO 9001: 2008. All QUBe units are to be tested to ISO 5801:2007 (airside performance) and BS 848 Part 2: 1985 (sound performance).

Technical Information
Dimensional Data

| Product Code | End Inlet Spigot Ø | A | B | C | D | Side Inlet W x H | Outlet W x H | Weight kg |
|---|---|---|---|---|---|---|---|---|
| SQU1/4HT | 315 | 500 | 195 | 30 | 60 | 221 x 440 | 203 x 440 | 44 |
| SQU2/4HT | 500 | 670 | 211 | 30 | 70 | 320 x 608 | 273 x 608 | 72 |
| SQU3/4HT | 560 | 820 | 255 | 40 | 70 | 420 x 740 | 304 x 740 | 106 |
| SQU4/4HT | 710 | 1020 | 292 | 40 | 85 | 550 x 940 | 373 x 940 | 173 |
| SQU4/6HT | 710 | 1020 | 292 | 40 | 85 | 550 x 940 | 373 x 940 | 186 |
All Dimensions expressed in mm.
Performance & Electrical Data
| Product Code | Speed r/min | Airflow SFP | Airflow m³/s @ Static Pressure Pa. | Overall Efficiency % | FMEG | Motor Electrical Data | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 0 | 100 | 200 | 250 | 300 | 350 | 400 | 450 | 500 | 550 | 600 | 700 | 800 | 900 | FLC Amps (Δ) | FLC Amps (Y) | Output kW | |||||
| SQU1/4-3HT | 1450 | m³/s | 0.58 | 0.47 | 0.35 | 0.27 | 0.16 | 33.4 | N50 | 1.4 | 0.8 | 0.25 | |||||||||
| W/(L/s) | 0.32 | 0.46 | 0.76 | 1.01 | 1.32 | ||||||||||||||||
| SQU2/4-3HT | 1440 | m³/s | 1.36 | 1.24 | 1.11 | 1.04 | 0.96 | 0.87 | 0.76 | 0.59 | 54.2 | N66 | 2.5 | 1.4 | 0.55 | ||||||
| W/(L/s) | 0.31 | 0.45 | 0.63 | 0.74 | 0.87 | 1.01 | 1.14 | 1.26 | |||||||||||||
| SQU3/4-3HT | 1470 | m³/s | 1.99 | 1.86 | 1.72 | 1.65 | 1.57 | 1.48 | 1.39 | 1.28 | 1.14 | 0.97 | 0.69 | 60.1 | N70 | 4.5 | 2.6 | 1.1 | |||
| W/(L/s) | 0.38 | 0.48 | 0.59 | 0.66 | 0.74 | 0.82 | 0.91 | 1.01 | 1.11 | 1.23 | 1.44 | ||||||||||
| SQU4/4-3HT | 1450 | m³/s | 3.88 | 3.72 | 3.55 | 3.46 | 3.37 | 3.28 | 3.18 | 3.08 | 2.98 | 2.86 | 2.74 | 2.46 | 2.08 | 1.45 | 64.8 | N70 | 11.3 | 7.5 | 3.0 |
| W/(L/s) | 0.49 | 0.59 | 0.71 | 0.77 | 0.83 | 0.91 | 0.99 | 1.07 | 1.17 | 1.27 | 1.37 | 1.59 | 1.79 | 2.00 | |||||||
| SQU4/6-3HT | 910 | m³/s | 3.01 | 2.86 | 2.67 | 2.55 | 2.41 | 2.24 | 2.03 | 1.76 | 1.37 | 66.9 | N76 | 6.7 | 3.9 | 1.5 | |||||
| W/(L/s) | 0.39 | 0.46 | 0.55 | 0.61 | 0.69 | 0.77 | 0.86 | 0.95 | 1.04 | ||||||||||||
FLC (Δ) at 230V/3Ph/50Hz.
FLC (Y) at 400V/3Ph/50Hz.Overall total efficiency, r/min and FMEG values are per ISO 12759 installation category D.
A variable speed drive (Eltadrive) must be installed with this fan.
Sound Data
| Product Code | Sound Power Level dBW @ Octave Band Hz | dBA @ 3m | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| 63Hz | 125Hz | 250Hz | 500Hz | 1 k Hz | 2 kHz | 4 kHz | 8 kHz | |||
| SQU1/4-3HT | Inlet | 62 | 66 | 70 | 70 | 66 | 62 | 57 | 53 | 51 |
| Outlet | 64 | 68 | 72 | 72 | 68 | 64 | 59 | 55 | 53 | |
| Breakout | 63 | 65 | 63 | 57 | 52 | 44 | 37 | 28 | 38 | |
| SQU2/4-3HT | Inlet | 68 | 72 | 76 | 76 | 72 | 68 | 63 | 59 | 57 |
| Outlet | 70 | 74 | 78 | 78 | 74 | 70 | 65 | 61 | 59 | |
| Breakout | 69 | 71 | 69 | 63 | 54 | 44 | 36 | 33 | 44 | |
| SQU3/4-3HT | Inlet | 72 | 76 | 79 | 79 | 75 | 71 | 67 | 62 | 60 |
| Outlet | 74 | 78 | 81 | 81 | 77 | 73 | 69 | 64 | 62 | |
| Breakout | 73 | 75 | 72 | 66 | 58 | 52 | 43 | 38 | 47 | |
| SQU4/4-3HT | Inlet | 78 | 82 | 86 | 85 | 81 | 77 | 73 | 68 | 66 |
| Outlet | 80 | 84 | 88 | 87 | 83 | 79 | 75 | 70 | 68 | |
| Breakout | 77 | 76 | 73 | 68 | 59 | 52 | 41 | 33 | 48 | |
| SQU4/6-3HT | Inlet | 73 | 76 | 79 | 78 | 74 | 70 | 65 | 61 | 59 |
| Outlet | 75 | 78 | 81 | 80 | 76 | 72 | 67 | 63 | 61 | |
| Breakout | 74 | 75 | 72 | 65 | 56 | 49 | 42 | 31 | 46 | |
Tests and preparation of the sound data have been carried out in accordance with BS 848 Part 2:1985 at 50% peak pressure.
The In-Duct Sound Power Level Spectra are in dB re-1pW.
The overall A-weighted sound pressure level is at a distance of 3m with spherical free-field propagation. It is expressed in dB re-20µPa and is presented for comparative purposes only.
Wiring Data
THREE Phase - 380V-415V / 50Hz
| Product Code | Wiring Diagram No. |
|---|---|
| SQU1/4HT | 152-600 |
| SQU2/4HT | 152-600 |
| SQU3/4HT | 152-600 |
| SQU4/4HT | 152-600 |
| SQU4/6HT | 152-600 |
Accessories
Inverter: IP20
This rating means this unit has a protection level of two against solid-body ingress, and a protection level of zero against the ingress of water.
Read more
Inverter: IP55
This rating means this unit has a protection level of five against solid-body ingress, and a protection level of five against the ingress of water.
Read more
Matching Flanges (061B)
Provides easy connection to flexible connector or ducting
Read more
Silencers (068-D**P)
Pre-galvanised sheet steel with perforated steel lining
Read more
Flexible Connectors (SLCS)
Fit to matching flanges to provide flexible connection
Read more
DCV Sensors
Demand Control Ventilation
Read more



Return to 