Heat Recovery Units

Heat Recovery Units

 
Left Arrow Return to Heat recovery / Products
 

Heat Recovery Units

komfovent main
 

The Komfovent heat recovery units are designed to create healthy indoor air quality and comfort in hotels, schools, nurseries, offices, conference halls and other premises. They are very efficient, easy to mount and maintain.

komfovent fb box

FEATURES & BENEFITS

Learn more about individual features and benefits of our products.

komfovent spec box

SPECIFICATION

The Heat Recovery range of hru fans as manufactured by Elta Fans Ltd.

Technical information

TECHNICAL INFORMATION

The technical information available to you from ELTA Fans is exhaustive - Choose from either sound, performance and electrical or dimensional data for each and every product

Accessories

ACCESSORIES

Elta supply a full range of accessories for each of their products.

Compare

COMPARE

Choose up to three products to compare their features side-by-side.

Downloads

DOWNLOADS

Get the full brochure, wiring diagrams and operation and maintenance instructions.

SPP Features and Benefits
 

Features & Benefits


Low profile

Casings are of compact design which allows ease of fitting.

Material strength

A robust unit with a double skin galvanised sheet steel casing in powder coat finish with fire resistant mineral wool infill for excellent sound characteristics.

Warranty

Komfovent Heat Recovery Unit has a 12 month warranty.

Performance

High efficiency pressed aluminium impellers are directly driven by an AC external rotor motor, designed to provide high performance characteristics.

Filtration

Units are equipped with compact, high quality air filters and filter monitoring providing customer notification of service period of filters.

Electrical

All units are suitable for 220-240V 1 phase operation or 380-440V 3 Phase dependant on model. All the AC motor specified units operate only on 50Hz whilst all EC motor specified units can operate on 50Hz or 60Hz

Quality assurance

All units are designed and manufactured with procedures as defined in BS EN ISO 9001: 2008.

SPP Specifications

Specification

Heat Recovery Units as manufactured by Elta Fans Ltd. 46 Third Avenue, Pensnett Trading Estate, Kingswinford, West Midlands, DY6 7US, UK. Tel: +44 (0) 1384 275800 - If you need more information - Contact us.


Heat Recovery

SREGO units incorporate a rotary heat exchanger which recovers heat up to 90%. Rotary heat exchangers work on the principle of heat recovery: A rotating aluminium rotor absorbs heat of the exhaust air and warms up the air supplied to the ventilated premises. SRECU units incorporate a plate heat exchanger which recovers heat up to 65%, the heat of the exhaust air is transferred to supply air through aluminium plates of the heat exchanger. Air flows through the heat exchanger crosswise. Unit design prevents cross contamination of the exhaust air with fresh air.


Casing

Panels are double skinned comprising two galvanised steel sheets, infilled with fire resistant thermal and sound attenuating insulation – mineral wool (l = 0,036W/mK). Units with 45 mm thick insulation may operate in unheated premises. Doors are manufactured with 45 mm insulation and equipped with locks. External casing surfaces are powder painted: RAL 7035 as standard preventing the unit from corrosion.


Control Elements

Units incorporate an Integrated control system which ensures safe operation of the unit, controls preset ventilation system parameters, and optimise unit operating costs. C3 and C4 controllers are used in SREGO / SRECU dependant on model.


Motors

The range of units may have either EC or AC external rotor motors fitted as standard. The motors contain sealed for life bearings.

 


Quality Management

All units in the Elta range are designed and manufactured to procedures as defined in BS EN ISO 9001:2008.


Typical Application

  • Hotels
  • Schools
  • Colleges
  • Libraries
  • Offices
  • Conference Halls
tech-ad

Technical Information


Dimensional Data

A - Fresh Air Intake
B - Supply Air
C - Extract
D - Exhaust Air
E - Bypass
F - Additional Extraction

SINGLE and THREE Phase

SRECU400HE-R-AC-C3
AC Motors


heat-1

SRECU700HE-R-AC-C3
AC Motors


hear-2

SRECU900HE-R-AC-C3
AC Motors


heat-3

SREGO250PE-B-EC-C4
EC Motors
heat-4

SREGO400-PE-B-EC-C4
EC Motors
heat-5

SRECU400HE-R-EC-C3
EC Motors
heat-6

SRECU700HE-R-EC-C3 & SRECU900HE-R-EC-C3
EC Motors
heat-7

SRECU1200HE-R-EC-C3
EC Motors
heat-8

SRECU1600HE-R-EC-C3 & SRECU2000HE-R-EC-C3
EC Motors
heat-9

Electrical Data

SRECU-250PE-B-AC-C4

Supply voltage 230V/1Ph/50Hz
FLC Amperes 5.10
Control system C4 / C4 PLUS
Nominal air flow m³/hr 250
Unit weight kg 40
Rotary heat exchangerSupplyExhaust
Thermal efficiency % 80
Energy recovery kW 2.3
Air temperature in/out &176;C -23 / +13.8 +20 / -16.8
 

Fan Motors
Input power Watts 58 x 2
Electric Air HeaterSupplyExhaust
Rating kW 1
 

SRECU-400PE-B-AC-C4

Supply voltage 230V/1Ph/50Hz
FLC Amperes 5.90
Control system C4 / C4 PLUS
Nominal air flow m³/hr 400
Unit weight kg 57
Rotary heat exchangerSupplyExhaust
Thermal efficiency % 83
Energy recovery kW 4.6
Air temperature in/out °C -23 / +13.8 +20 / -16.8
 

Fan Motors
Input power Watts 135 x 2
Electric Air HeaterSupplyExhaust
Rating kW 1
 

SRECU400HE-R-EC-C3

Supply voltage 230V/1Ph/50Hz
FLC Amperes 10.7
Control system C3
Nominal air flow m³/hr 400
Unit weight kg 55
Plate heat exchangerSupplyExhaust
Thermal efficiency % 58.8 / 52.9
Energy recovery kW 2.4
Air temperature in/out °C -10 / +7.6 20 / 4.5
Relative humidity in/out °C 82 / 20.3 45 / 97
 

Fan Motors
Input power Watts 105 x 2
Speed r/min 3570
Electric Air HeaterSupplyExhaust
Rating kW 2
Air temperature in/out kW 7.6 / 22
 

SRECU400HE-R-AC-C3

Supply voltage 230V/1Ph/50Hz
FLC Amperes 10.1
Control system C3
Nominal air flow m³/hr 400
Unit weight kg 55
Plate heat exchangerSupplyExhaust
Thermal efficiency % 58.8 / 52.9
Energy recovery kW 2.4
Air temperature in/out °C -10 / +7.6 20 / 4.5
Relative humidity in/out °C 82 / 20.3 45 / 97
 

Fan Motors
Input power Watts 135 x 2
Speed r/min 2650
Electric Air HeaterSupplyExhaust
Rating kW 2
Air temperature in/out kW 7.6 / 22
 

SRECU400HE-R-AC-C3

Supply voltage 230V/1Ph/50Hz
FLC Amperes 10.1
Control system C3
Nominal air flow m³/hr 400
Unit weight kg 55
Plate heat exchangerSupplyExhaust
Thermal efficiency % 58.8 / 52.9
Energy recovery kW 2.4
Air temperature in/out °C -10 / +7.6 20 / 4.5
Relative humidity in/out °C 82 / 20.3 45 / 97
 

Fan Motors
Input power Watts 135 x 2
Speed r/min 2650
Electric Air HeaterSupplyExhaust
Rating kW 2
Air temperature in/out kW 7.6 / 22

SRECU700HE-R-EC-C3

Supply voltage 230V/1Ph/50Hz
FLC Amperes 13.7
Control system C3
Nominal air flow m³/hr 700
Unit weight kg 75
Plate heat exchangerSupplyExhaust
Thermal efficiency % 57.6 / 51.9
Energy recovery kW 4
Air temperature in/out °C -10 / +7.3 20 / 4.7
Relative humidity in/out °C 82 / 20.8 45 / 96
 

Fan Motors
Input power Watts 164 x 2
Speed r/min 2570
Electric Air HeaterSupplyExhaust
Rating kW 2.5
Air temperature in/out kW 7.3 / 18
 

SRECU700HE-R-AC-C3

Supply voltage 230V/1Ph/50Hz
FLC Amperes 12.9
Control system C3
Nominal air flow m³/hr 700
Unit weight kg 75
Plate heat exchangerSupplyExhaust
Thermal efficiency % 57.6 / 51.9
Energy recovery kW 4
Air temperature in/out °C -10 / +7.3 20 / 4.7
Relative humidity in/out °C 82 / 20.8 45 / 96
 

Fan Motors
Input power Watts 240 x 2
Speed r/min 2800
Electric Air HeaterSupplyExhaust
Rating kW 2.5
Air temperature in/out kW 7.3 / 18
 

SRECU900HE-R-AC-C3

Supply voltage 400V/3Ph/50Hz
FLC Amperes 10.3
Control system C3
Nominal air flow m³/hr 900
Unit weight kg 78
Plate heat exchangerSupplyExhaust
Thermal efficiency % 56.5 / 50.9
Energy recovery kW 5.1
Air temperature in/out °C -10 / +7 20 / 4.7
Relative humidity in/out °C 82 / 21.3 45 / 96
 

Fan Motors
Input power Watts 235 x 2
Speed r/min 2780
Electric Air HeaterSupplyExhaust
Rating kW 4.5
Air temperature in/out kW 7 / 22
 

SRECU1200HE-R-AC-C3

Supply voltage 400V/3Ph/50Hz
FLC Amperes 13.9
Control system C3
Nominal air flow m³/hr 1200
Unit weight kg 195
Plate heat exchangerSupplyExhaust
Thermal efficiency % 52
Energy recovery kW 6.3
Air temperature in/out °C -10 / +5.7 20 / 6.1
Relative humidity in/out °C 82 / 26 45 / 100
 

Fan Motors
Input power Watts 490 x 2
Speed r/min 1480
Electric Air HeaterSupplyExhaust
Rating kW 6
Air temperature in/out kW 5.9 / 20.9
 

SRECU1600HE-R-AC-C3

Supply voltage 400V/3Ph/50Hz
FLC Amperes 26.6
Control system C3
Nominal air flow m³/hr 1600
Unit weight kg 320
Plate heat exchangerSupplyExhaust
Thermal efficiency % 60.3
Energy recovery kW 9.7
Air temperature in/out °C -10 / +8.1 20 / 5.2
Relative humidity in/out °C 82 / 20 45 / 95
 

Fan Motors
Input power Watts 650 x 2
Speed r/min 1480
Electric Air HeaterSupplyExhaust
Rating kW 12
Air temperature in/out kW -2.8 / +20
 

SRECU2000HE-R-AC-C3

Supply voltage 400V/3Ph/50Hz
FLC Amperes 38.8
Control system C3
Nominal air flow m³/hr 2000
Unit weight kg 325
Plate heat exchangerSupplyExhaust
Thermal efficiency % 51.9
Energy recovery kW 10.4
Air temperature in/out °C -10 / +5.6 20 / 6.9
Relative humidity in/out °C 82 / 23 45 / 90
 

Fan Motors
Input power Watts 830 x 2
Speed r/min 1480
Electric Air HeaterSupplyExhaust
Rating kW 12
Air temperature in/out kW -2.8 / +20
 

Sound Data

Product CodeSound Power Level dBW @ Octave Band HzdB(A) @ 3m
63 Hz 125 Hz 250 Hz 500 Hz 1k Hz 2k Hz 4k Hz 8k Hz
SREGO-250PE-B-AC-C4 Supply Inlet 55 49 47 48 50 47 46 40 34
Outlet 59 59 58 57 57 55 53 51 42
Extract Inlet 55 49 58 57 57 55 53 51 41
Outlet 59 51 47 48 50 49 47 45 35
Break Out 37 37 36 36 36 34 34 33 21
SREGO-400PE-B-AC-C4 Supply Inlet 58 60 60 61 56 50 44 38 41
Outlet 62 69 71 71 66 58 53 48 51
Extract Inlet 58 60 60 61 56 50 44 38 41
Outlet 62 69 71 71 66 58 53 48 51
Break Out 49 53 52 43 38 30 22 17 26
SRECU400HE-R-EC-C3 Supply Inlet 52 54 55 55 51 46 42 38 35
Outlet 54 59 60 60 56 50 47 43 40
Extract Inlet 52 54 55 55 51 46 42 38 35
Outlet 54 59 60 60 56 51 47 44 40
Break Out 37 40 40 33 30 25 20 16 15
SRECU400HE-R-AC-C3 Supply Inlet 50 53 55 55 49 43 37 32 34
Outlet 53 59 61 61 56 48 44 39 41
Extract Inlet 50 53 55 55 49 43 37 32 34
Outlet 53 59 61 61 56 49 44 40 41
Break Out 35 39 37 29 25 18 11 6 12
SRECU700HE-R-EC-C3 Supply Inlet 54 56 57 57 53 48 44 40 38
Outlet 56 61 62 62 58 52 49 45 42
Extract Inlet 54 56 57 57 53 48 44 40 38
Outlet 56 61 62 62 58 53 49 46 43
Break Out 39 42 42 35 32 27 22 18 18
SRECU700HE-R-AC-C3 Supply Inlet 60 63 65 65 59 53 47 42 44
Outlet 63 69 71 71 66 58 54 49 51
Extract Inlet 60 63 65 65 59 53 47 42 44
Outlet 63 69 71 71 66 59 54 50 51
Break Out 45 49 47 39 35 28 21 16 22
SRECU900HE-R-AC-C3 Supply Inlet 58 61 63 63 57 51 45 40 42
Outlet 61 67 69 69 64 56 52 47 49
Extract Inlet 58 61 63 63 57 51 45 40 42
Outlet 61 67 69 69 64 57 52 48 49
Break Out 43 47 45 37 33 26 19 14 20
SRECU1200HE-R-AC-C3 Supply Inlet 46 49 51 51 45 39 33 28 30
Outlet 49 55 57 57 52 44 40 35 36
Extract Inlet 46 49 51 51 45 39 33 28 30
Outlet 49 55 57 57 52 45 40 36 36
Break Out 31 35 33 25 21 14 7 2 7
SRECU1600HE-R-AC-C3 Supply Inlet 49 52 54 54 48 42 36 31 33
Outlet 52 58 60 60 55 47 43 38 40
Extract Inlet 49 52 54 54 48 42 36 31 33
Outlet 52 58 60 60 55 48 43 39 40
Break Out 34 38 36 28 24 17 10 5 11
SRECU2000HE-R-AC-C3 Supply Inlet 48 50 50 50 46 40 35 29 30
Outlet 50 55 55 56 53 45 41 36 36
Extract Inlet 48 50 50 50 46 40 35 29 30
Outlet 50 55 55 56 53 46 42 37 37
Break Out 34 38 36 28 24 17 10 5 11

Tests and preparation of the sound data have been carried out in accordance with BS 848 Part 2:1985 at 50% peak pressure.
The In-duct Sound Power Level Spectra are in dB re-1pW.
The overall A-weighted sound pressure level is at a distance of 3m with spherical free-field propagation. It is expressed in dB re-20µPa and is presented for comparative purposes only.

Accessories

  • Non-Return Dampers (018)

    Prevents reverse flow of air when fan not operating

    Read more
  • Fast Clamps (018)

    For quick connection of spigotted fans to circular duct or accessories

    Read more
  • Silencers (068-JF)

    Pre-galvanised sheet steel with perforated steel lining

    Read more
 

SINGLE Phase - 220v to 240v / 50Hz
AC Motors

Product CodeClamps (each)DamperSilencer 300mm LongSilencer 600mm LongSilencer 900mm LongSilencer 1200mm LongRemote Communication UnitEnhanced Control Unit
SRECU400HE-R-AC-C3 018-200-CLAMP 018-200-DAMPER 068-0200-JF1 068-0200-JF2 068-0200-JF3 068-0200-JF4 149-PING -
SRECU700HE-R-AC-C3 018-0250-CLAMP 018-250-DAMPER 068-0250-JF1 068-0250-JF2 068-0250-JF3 068-0250-JF4 149-PING -

THREE Phase - 380v to 415v / 50Hz
AC Motors

Product CodeClamps (each)DamperSilencer 300mm LongSilencer 600mm LongSilencer 900mm LongSilencer 1200mm LongRemote Communication UnitEnhanced Control Unit
SRECU900HE-R-AC-C3 018-250-CLAMP 018-250-DAMPER 068-0250-JF1 068-0250-JF2 068-0250-JF3 068-0250-JF4 149-PING -

SINGLE Phase - 220v to 240v / 50Hz
EC Motors

Product CodeClamps (each)DamperSilencer 300mm LongSilencer 600mm LongSilencer 900mm LongSilencer 1200mm LongRemote Communication UnitEnhanced Control Unit
REGO250PE-B-EC-C4 018-160-CLAMP 018-160-DAMPER 068-0160-JF1 068-0160-JF2 068-0160-JF3 068-0160-JF4 149-PING 149-C4PLUS
REGO400PE-B-EC-C4 018-200-CLAMP 018-200-DAMPER 068-0200-JF1 068-0200-JF2 068-0200-JF3 068-0200-JF4 149-PING 149-C4PLUS
SRECU400HE-R-EC-C3 018-200-CLAMP 018-200-DAMPER 068-0200-JF1 068-0200-JF2 068-0200-JF3 068-0200-JF4 149-PING -
SRECU400HE-R-AC-C3 018-200-CLAMP 018-200-DAMPER 068-0200-JF1 068-0200-JF2 068-0200-JF3 068-0200-JF4 149-PING -
SRECU700HE-R-EC-C3 018-0250-CLAMP 018-250-DAMPER 068-0250-JF1 068-0250-JF2 068-0250-JF3 068-0250-JF4 149-PING -
SRECU700HE-R-AC-C3 018-0250-CLAMP 018-250-DAMPER 068-0250-JF1 068-0250-JF2 068-0250-JF3 068-0250-JF4 149-PING -

THREE Phase - 380v to 415v / 50Hz


EC Motors

Product CodeClamps (each)DamperSilencer 300mm LongSilencer 600mm LongSilencer 900mm LongSilencer 1200mm LongRemote Communication UnitEnhanced Control Unit
RECU900HE-R-EC-C3 018-250-CLAMP 018-250-DAMPER 068-0250-JF1 068-0250-JF2 068-0250-JF3 068-0250-JF4 149-PING
RECU1200HE-R-EC-C3 018-315-CLAMP 018-315-DAMPER 068-0315-JF1 068-0315-JF2 068-0315-JF3 068-0315-JF4 149-PING -
RECU1600HE-R-EC-C3 018-355-CLAMP 018-355-DAMPER 068-0355-JF1 068-0355-JF2 068-0355-JF3 068-0355-JF4 149-PING -
RECU2000HE-R-EC-C3 018-355-CLAMP 018-355-DAMPER 068-0355-JF1 068-0355-JF2 068-0355-JF3 068-0355-JF4 149-PING -