- Air volume flow rates of up to 4.57 m3/s
- Static pressures of up to 1000 Pa.
- Motors standard squirrel cage induction, mounted out of the air stream.
- Motors IP54 protection and Class F insulation.
- Suitable for operating temperatures up to 50° C.
>Learn more about roof fans
Compare
The Heritage SCHT is a range of roof mounted centrifugal fans which is designed to handle clean, grease laden or contaminated air, whilst providing easy access for cleaning
FEATURES & BENEFITSLearn more about individual features and benefits of our products. |
SPECIFICATIONThe Heritage SCHT range of roof mounted fans as manufactured by Elta Fans Ltd. |
TECHNICAL INFORMATIONThe technical information available to you from ELTA Fans is exhaustive - Choose from either sound, performance and electrical or dimensional data for each and every product |
ACCESSORIESElta supply a full range of accessories for each of their products. |
COMPAREChoose up to three products to compare their features side-by-side. |
DOWNLOADSGet the full brochure, wiring diagrams and operation and maintenance instructions. |
Features & Benefits
Material strength
The all metal cowls have a robust, long lasting construction, manufactured from galvanised steel and powder coated after forming.
Impeller design
Aerodynamically designed backward curved centrifugal impellers in either sheet steel or aluminium dependant upon impeller selection.
Tested to the very latest standards
SCHT units are tested to ISO 5801:1997 (airside performance) and to BS 848 Pt 2:1985 (sound performance) meaning accurate, up to date information on performance and noise data that can be relied upon..
Quality assurance
All units are designed and manufactured with procedures as defined in BS EN ISO 9001: 2008.
Easy cleaning
The wind band is held in place with toggle clamps to permit easy access for cleaning and maintenance when the units are installed in atmospheres that are dirt laden
High temperature
With motors out of the air stream, the SCHT is suitable for a wide range of applications from contaminated air to elevated temperatures.
Reliability
Motors have sealed for life bearings.

Specification
The Heritage SCHT range of roof mounted extract fans as manufactured by Elta Fans Ltd. 46 Third Avenue, Pensnett Trading Estate, Kingswinford, West Midlands DY6 7US, UK, Tel: +44 (0) 1384 275800 - If you need more information - Contact us.
Casing
The all metal cowls shall provide a long lasting and robust construction, manufactured from pressed galvanised sheet steel and powder coated after forming
The wind band shall incorporate quick-release toggle clamps to provide easy access for cleaning and maintenance.
All SCHT units can be mounted at angles up to 15℃.
Motors
Motors are to be foot mounted totally enclosed metric type to IP55, with sealed for life bearings, standard industrial paint finish and Class F insulation to EN 60034-5, suitable for operating temperatures of up to +50℃.
Motors are to be wired via a weatherproofed cable to an IP55 protected terminal box.
Impellers
Aerodynamically designed backward curved centrifugal impellers constructed in aluminum or galvanised sheet steel.
Motor and impeller are balanced to quality class G6.3.
Quality Management
Units are to be designed and manufactured with procedures as defined in BS EN ISO 9001: 2008.
All SCHT units are to be tested to ISO 5801:1997 (airside performance) and BS 848 Part 2: 1985 (sound performance).

Technical Information
Dimensional Data

| Product Code | A | B | C | D | E | F | Weight kg | |
|---|---|---|---|---|---|---|---|---|
| 4 Pole | 6 Pole | |||||||
| SCHT315 | 520 | 310 | 430 | 50 | 310 | 410 | 16 | |
| SCHT350 | 665 | 420 | 520 | 50 | 400 | 500 | 26 |
|
| SCHT400 | 665 | 420 | 520 | 50 | 400 | 500 | ||
| SCHT450 | 900 | 540 | 740 | 60 | 620 | 720 | 49 | |
| SCHT500 | 900 | 540 | 740 | 60 | 620 | 720 | 57 | 51 |
| SCHT560 | 900 | 540 | 740 | 60 | 620 | 720 | 65 | 56 |
| SCHT630 | 1160 | 665 | 830 | 60 | 710 | 810 | 97 | 78 |
Performance & Electrical Data
THREE Phase - 380V-415V / 50Hz
| Product Code | Speed r/min | Airflow m3/s Static Pressure Pa. | Motor Electrical Data | Sound Level dBA@3m | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
0 |
50 |
100 |
150 |
200 |
250 |
300 |
400 |
500 |
600 |
800 |
1000 |
FLC Amps |
SC Amps |
Output Kw |
|||
| SCHT315/6-3 | 960 | 0.34 | 0.29 | 0.11 | 1.30 | 7.80 | 0.37 | 41 | |||||||||
| SCHT315/4-3 | 1440 | 0.53 | 0.50 | 0.45 | 0.41 | 0.35 | 0.28 | 1.20 | 7.20 | 0.37 | 47 | ||||||
| SCHT350/6-3 | 960 | 0.53 | 0.43 | 0.31 | 0.18 | 1.30 | 7.80 | 0.37 | 42 | ||||||||
| SCHT350/4-3 | 1440 | 0.84 | 0.78 | 0.73 | 0.68 | 0.62 | 0.55 | 0.45 | 1.50 | 9 | 0.55 | 51 | |||||
| SCHT400/6-3 | 960 | 0.77 | 0.67 | 0.58 | 0.47 | 1.30 | 7.80 | 0.37 | 44 | ||||||||
| SCHT400/4-3 | 1440 | 1.12 | 1.08 | 1.03 | 0.97 | 0.91 | 0.84 | 0.76 | 0.52 | 1.50 | 9 | 0.55 | 54 | ||||
| SCHT450/6-3 | 960 | 1.05 | 0.98 | 0.90 | 0.78 | 0.63 | 1.30 | 7.80 | 0.37 | 46 | |||||||
| SCHT450/4-3 | 1440 | 1.61 | 1.54 | 1.48 | 1.41 | 1.35 | 1.28 | 1.22 | 1.06 | 0.83 | 1.50 | 9 | 0.55 | 56 | |||
| SCHT500/6-3 | 960 | 1.39 | 1.33 | 1.26 | 1.18 | 1.06 | 0.87 | 1.30 | 7.80 | 0.37 | 49 | ||||||
| SCHT500/4-3 | 1440 | 2.24 | 2.18 | 2.11 | 2.04 | 1.97 | 1.89 | 1.81 | 1.63 | 1.42 | 1.14 | 2.90 | 17.40 | 1.10 | 60 | ||
| SCHT560/6-3 | 960 | 2.14 | 2.04 | 1.92 | 1.79 | 1.65 | 1.49 | 1.29 | 1.80 | 10.80 | 0.55 | 53 | |||||
| SCHT560/4-3 | 1440 | 3.22 | 3.11 | 3.03 | 2.95 | 2.87 | 2.80 | 2.73 | 2.58 | 2.42 | 2.23 | 1.49 | 4.80 | 28.80 | 2.20 | 65 | |
| SCHT630/6-3 | 960 | 2.80 | 2.73 | 2.65 | 2.56 | 2.46 | 2.34 | 2.19 | 1.72 | 3.40 | 20.40 | 1.10 | 57 | ||||
| SCHT630/4-3 | 1440 | 4.57 | 4.48 | 4.39 | 4.29 | 4.20 | 4.10 | 4 | 3.80 | 3.58 | 3.36 | 2.83 | 2.07 | 8.03 | 48.20 | 4 | 70 |
Sound levels are average spherical free field values at 50% peak pressure for comparative purposes only.


Sound Data
SCHT - THREE Phase
| Product Code | 63Hz | 125Hz | 250Hz | 500Hz | 1kHz | 2kHz | 4kHz | 8kHz | dBA@3M |
|---|---|---|---|---|---|---|---|---|---|
| SCHT315/4-3 | 81 | 77 | 69 | 66 | 58 | 58 | 56 | 50 | 47 |
| SCHT350/4-3 | 79 | 77 | 73 | 70 | 61 | 63 | 62 | 52 | 51 |
| SCHT400/4-3 | 82 | 80 | 75 | 72 | 65 | 66 | 66 | 59 | 54 |
| SCHT450/4-3 | 84 | 82 | 77 | 74 | 68 | 69 | 69 | 65 | 56 |
| SCHT500/4-3 | 87 | 87 | 82 | 76 | 73 | 73 | 73 | 70 | 60 |
| SCHT560/4-3 | 91 | 92 | 88 | 79 | 78 | 77 | 77 | 75 | 65 |
| SCHT630/4-3 | 94 | 98 | 94 | 82 | 83 | 81 | 82 | 80 | 70 |
| SCHT315/6-3 | 76 | 68 | 64 | 60 | 54 | 54 | 48 | 42 | 41 |
| SCHT350/6-3 | 76 | 68 | 65 | 62 | 57 | 51 | 46 | 43 | 42 |
| SCHT400/6-3 | 77 | 72 | 66 | 63 | 58 | 54 | 51 | 47 | 44 |
| SCHT450/6-3 | 77 | 76 | 67 | 64 | 59 | 57 | 55 | 51 | 46 |
| SCHT500/6-3 | 80 | 79 | 72 | 66 | 62 | 60 | 58 | 56 | 49 |
| SCHT560/6-3 | 83 | 83 | 77 | 69 | 66 | 64 | 62 | 61 | 53 |
| SCHT630/6-3 | 86 | 87 | 82 | 72 | 70 | 68 | 66 | 66 | 57 |
Wiring Data
THREE Phase - 380V-415V / 50Hz
| Product Code | Wiring Diagram no. |
|---|---|
| SCHT315/4-3 | 152-600 |
| SCHT315/6-3 | 152-600 |
| SCHT350/4-3 | 152-600 |
| SCHT350/6-3 | 152-600 |
| SCHT400/4-3 | 152-600 |
| SCHT400/6-3 | 152-600 |
| SCHT450/4-3 | 152-600 |
| SCHT450/6-3 | 152-600 |
| SCHT500/4-3 | 152-600 |
| SCHT500/6-3 | 152-600 |
| SCHT560/4-3 | 152-600 |
| SCHT560/6-3 | 152-600 |
| SCHT630/4-3 | 152-601 |
| SCHT630/6-3 | 152-600 |
Accessories
Inverter: IP20
This rating means this unit has a protection level of two against solid-body ingress, and a protection level of zero against the ingress of water.
Read more
Inverter: IP55
This rating means this unit has a protection level of five against solid-body ingress, and a protection level of five against the ingress of water.
Read more